Earth leakage circuit breaker 4P 30mA Type B 32A curve B
Earth leakage circuit breaker 30mA type B and automatic current switch 32A curve B in 1 device.
You can place this earth leakage circuit breaker in front of any charging station if it is connected with a cable with a section of at least 6mm².
You place this in the circle just behind the main differential 300mA Type B.
Attention! If a 300mA Type A main differential has been installed, it must be replaced by a Type B OR you place a 300mA Type B earth leakage circuit breaker in parallel next to the Type A main differential.
For this you use an earth leakage circuit breaker 4P 300mA Type B 63A or 100A
- Total number of poles: 4
- Number of protected poles: 4
- Rated voltage: 400 V
- Rated current: 32 A
- Rated fault current: 0.03 A (30mA)
- Type of leakage current: B
- Nominal breaking capacity according to EN 61009: 10 kA
- Rated breaking capacity IEC 60947-2: 6 kA
- Rated short-circuit breaking capacity Icn according to EN 61009-1: 6 kA
- Surge voltage resistance: 0.25 kA
- Voltage type: AC Frequency: 50 Hz Trip characteristic: B
- Switching zero: Yes
- With locking device: No
- Width in module units: 3
- Connectable conductor cross-section single-wire: 0.75 - 16 mm²
- Connectable conductor cross-section multi-wire: 0.75 - 10 mm²